Input Power Installation (continued)
Figure 5
Hot
Neutral
(
Black)    (White)
Equipment
Ground (Green)
Note: Refer to Figure 5 for the following
procedure.
1.
2.
Ensure the controller power source is off.
Remove the switch cover plate and switch
from the input power junction box.
Note: The switch is attached to the black
transformer wire. Use care when removing the
switch to prevent straining this connection.
3.
Remove the conduit access knock-out plug
in the bottom left corner of the  junction box
and install 3/4" electrical conduit to as
shown.
Switch
Note: The access opening in the junction
box is for 1/2" conduit. A 1/2" to 3/4" conduit
adapter will be required.
3/4"
Electrical
Conduit
Switch
Cover Plate
4.
5.
Route the Hot, Neutral and Equipment
Ground wires from the power source into
the junction box.
Strip 1/2" (13 mm) insulation from the  Hot
(black) wire and secure to the remaining
switch terminal. Using insulated wire
connectors, splice the Neutral (white) wire to
the white transformer wire and the
Equipment Ground (green) wire to the green
transformer wire.
Wiring From
Power Source
6.
Reposition and secure the switch and cover
plate. Ensure the switch is set to  the Off
(down) position.
Figure 6
Field Wire Installation
CM
1
1.
2.
3.
4.
To provide a field common wire, attach  one
wire to either solenoid lead of all  valves to
be operated by the controller.
48
37
1
2
Attach a separate power wire to each remain-
ing solenoid lead. Label these wires for identi-
fication at the station output modules.
4
Using an approved waterproof splicing
method, properly insulate all valve solenoid
wire connections.
12
C
Route the field wires into the controller cabinet
through 2" conduit. Remove approximately 3/8"
C
13
(10
mm) insulation from the ends of each wire.
Connect the valve common wire(s) to terminal
Cof any station output module.
36
5.
6.
Connect each valve power wire to the
appropriate station number terminal.
See Figure 6.
3
24
25
Caution: Maximum  current load per
station must  not exceed 0.5A.
C
7.
If a 24  V a.c. pump start  relay or master
valve is used,  connect the power  wire to
terminal M”  of station output  module
number 1 and  the common wire  to terminal Cof any station output module.
Note: The Master  (M) terminal on  station output modules  24 is inoperative.
Caution: The pump start relay current load must not exceed 0.5A. Do  not connect the  pump starter directly  to
the controllerdamage  to the controller  will result.
4
Product Specification
CategoriesLawn Mower Manual, Sprinkler and Irrigation Manuals, Toro Sprinkler and Irrigation Manuals
Download File
Please Enter the Security Characters Shown Below. Letters are Case Sensitive. Your download link will appear upon completing this step.
- 6 pages
Document TypeCatalog
LanguageEnglish
Product BrandToro. Customer Service Representatives are available by phone: Monday - Friday 7:30 a.m. to 9:00 p.m. (CDT) - Saturday 8:00 a.m. to 8:00 p.m. (CDT) - Sunday 10:00 a.m. to 8:00 p.m. (CDT)
Canada 1-888-225-4886 USA 1-888-384-9939, Lawn Mower
Document File TypePDF
Publishertoro.com
Wikipedia's PageToro Company
CopyrightAttribution Non-commercial
(0 votes, average: 0 out of 5)

Submit your review (optional)
(will not be displayed)
* Required Field

Leave a Reply

Your email address will not be published. Required fields are marked *

*
*
Website